Pressure Controller & Two Stage Pressure Control Valve  :  Model 132-060

Specifications & Materials    Descriptions & Typical Applications   Contoller Specification & Work  Principle

¢º Special Feature 

 

¡Ü Accurate Pressure Control

¡Ü Two Adjustable Setpoints

¡Ü Easy Adjustment and Maintenance

¡Ü Easy Program

¡Ü Controller with a built-in Battery


    Model 132-060 consists of Basic Valve(BALEM 130), Two Pressure Reducing Pilot Valve(Model 562) and Valve Control Device(Model VCD-01). It has one pilot set at a higher pressure setting for times of high water demand; a second pilot set at a lower pressure setting for low demand. This valve is suitable for many pressure control applications for high two-pressure control of a distribution zone

    Controller can be used without electric power because of a built-in battery and also program is easily set by remote control.

  

 

¢º Patent


* Korea Patent No. : 0540596

 

¢º Specifications 

 

Specifications

Screwed 

KSPT(BSP) - NPT Standard

Flanged

10kgf/§² - ANSI 150 Standard

Globe

50A(2¢©) ¢¦80A(3¢©)

50A(2¢©) ¢¦300A(12¢©)

Angle

50A(2¢©) ¢¦80A(3¢©)

50A(2¢©) ¢¦300A(12¢©)

  

  

¢º Operating Pressure

 

 

KS D 1513. Class 10

ANSI B 16.42 Class 150

Operating Pressure

0.05¢¦1.5 MPa(0.5~15kg f/§²)

7¢¦213 PSIG

Media

Temperature :  0°C ~ 80°C  Water, Oil (Order-Made)

  

 

¢º Solenoid Control Valve Specifications

  

Voltage

  6.0V DC

Operating Pressure

  1.5 MPa(213 PSIG)

Level

  Coil Insulation Class H

Power Supply

  DC 3 Watts

  

¢º Description 

 

Item

  Description

1

  BALEM 130 (Basic Valve)

2

  Pressure Reducing Pilot Valve (Model 562)

3

  Strainer

4

  Hytrol Valve

5

  3-Way Solenoid Valve

6

  Controller (Model VC-01)

7

  Needle Valve

8

  Cock Valve

9

  Pressure Gauge

 

      Control Diagram

 

¢º Typical Applications

¡Ø Click E-catalog  to Download.                     

  

¢º Controller Specifications

 

Minuteness

  1 minute per month

Battery(year)

  Over 5 year

Size(mm)

  130 X 80 X 70

Weight(kps)

  1 Kg

  

 

¢º Controller Working Mode

 

¡Ü Test Mode

    In test mode, it can be changed a pre-set high pressure Pressure Reducing Valve with a pre-set high pressure for a while during the pre-set time. So, It can be checked whether it is working or not at the spot.

¡Ü Programable Mode

    In programmable Mode, It can be set at a higher pressure setting for times of high water demand; and set at a lower pressure setting for low demand according to each day (Mon~Sun) as Automatic mode. There are 2 period mode and 4 period mode.

              

  

 

¢º Work Principle

 

¡Ü High Pressure Reducing Feature

Step.1  In high demand, 3-Way Solenoid Valve "E" that changes            position automatically when directed by Controller

Step.2  High pressure flow goes Inlet Pilot "A" ¢¡ Hytol Valve "B" and            Upper chamber of Diaphragm

Step.3  Flow when Hytol Valve "B" is opened goes High pressure            setting Pressure Pilot valve "C"

Step.4  Flow through High pressure setting Pressure Pilot Valve "C"            goes Low Pressure Setting pilot valve "D" and Outlet Pilot "F"

Step.5  Low Pressure Setting Pilot Valve "D" closes after sensing            High Pressure from Pressure Reducing Pilot valve "C"

Step.6  High Pressure setting Pilot Valve "C" open, Flow through            Upper chamber of Diaphragm reduced relatively and High            Pressure Setting Reducing Valve is working

¡Ü Low Pressure Reducing Feature

Step.1  In Low demand, 3-Way valve "E" that changes position            automatically when directed by Controller.

Step.2  High pressure flow goes Inlet Pilot "A" ¢¡ Solenoid Valve "E",            Low pressure setting Pilot Valve "D" and Upper chamber of            Diaphragm

Step.3  Flow into Solenoid Valve ¡°E¡± goes ¢¡ Upper chamber of            Hytrol valve ¡°B¡± so Hytrol Vavle "B"is close and High            pressure setting pilot "C" is closed

Step.4  Low Pressure Setting Pilot Valve "D" open, Flow from Inlet            Pilot Valve "A" goes Low Pressure setting Pilot Valve "D" ¢¡            Outlet Pilot Valve ¡°F¡±

Step.5  Low Pressure setting Pilot Valve "D" open, Flow through            Upper chamber of Diaphragm reduced relatively and Low            Pressure Setting Reducing Valve is working.

 Copyright (c) 2005  Balem Co. Ltd.,  All rights reserved.