Booster Pump Control Valve : Model 139-010

Specifications & Materials     Descriptions & Typical Applications  
Sequence of Operation          Dimentions & Installation  

¢º Special Feature 

  

¡Ü Provides quick check action

¡Ü Operates using pressure in the pipe

¡Ü Adjustable the speed of opening and closing separately


     Booster Pump Control Valve is designed for installation on booster pump's discharge side to prevent starting and stopping pressure surges in the pipeline while the pump starts and stops.

     If power failure occurs, the valve immediately closes preventing return flow, regardless of control mode.


 

¢º Patent


* Korea Patent No. : 0479297
 
 

¢º Specifications 

  

Specifications

Screwed 

KSPT(BSP) - NPT Standard

Flanged

10kgf/§² - ANSI 150 Standard

Globe

50A(2¢©) ¢¦80A(3¢©)

50A(2¢©) ¢¦300A(12¢©)

Angle

50A(2¢©) ¢¦80A(3¢©)

50A(2¢©) ¢¦300A(12¢©)

 

 

¢º Operating Pressure

 

 

KS D 1513. Class 10

ANSI B 16.42 Class 150

Operating Pressure

0.05¢¦1.5 MPa(0.5~15kg f/§²)

7¢¦213 PSIG

Media

Temperature :  0°C ~ 80°C  Water, Oil (Order-Made)

  

 

¢º Materials 

 

Compartment

Material Options

Body & Cover

Ductile Iron

SSC13

Diaphragm Washer & Disc

Cast Iron

SSC13

Cover Plug & Bearing

Brass

STS304

Shaft & Seat

STS304

Diaphragm

Nylon reinforced N.R

Disc Seal

N.R

  Note :  · NSF/ANSI Standard 61 Epoxy Coating standard

            ·  Nylon 11 Coating available (Rilsan Coating) : optional

 

 

¢º Solenoid Control Valve Specifications

 

Voltage

  24, 110, 220 AC 60Hz or 50Hz / 12, 24 DC

Operating Pressure

  1.5 MPa (213 PSIG)

Coil Insulation

  Coil Insulation Class B(Standard) H(Optional)

Power Supply

  AC 8 Watts / DC 12 Watts

 

¢º Description 

 

Item

  Description

1

  BALEM 130 (Basic Valve)

2

  Strainer

3

  Cock Valve

4

  Suttle Valve

5

  3-Way Solenoid control Valve

6

  Flow Control Valve

7

  3-Way Solenoid control Valve

8

  Flow Control Valve

9

  Cock Valve

10

  Flow Clean Strainer

           Control Diagram

  

¢º Typical Applications

 

¡Ø Click E-catalog  to Download.        

  

¢º Sequence Of Operation

 

¡Ü Pump Off

   With pump off, static line pressure is transmitted through strainer ¡°F"¡æshuttle Valve ¡°B"¡æsolenoid valve 1¡æspeed control ¡°D"¡æthe chamber above the diaphragm, thus holding the valve closed.
     If power failure occurs, the valve closes immediately to prevent reverse flow, regardless of control mode.

  

¡Ü Starting Cycle

   Starting switch closes, pump starts, solenoid control valve 1 energizes and shifts allowing fluid from upper diaphragm chamber to drain to atmosphere.
    High pressure fluid from pump enters strainer "A"¡æshuttle valve ¡°B"¡æsolenoid valve 2¡æspeed control valve ¡°C"¡æHigh pressure fluid is transmitted to the lower diaphragm chamber and opens the valve slowly.

 

¡Ü Stopping Cycle

   Starting switch opens, solenoid control 2 de-energizes and shifts, pump continues to run. High Pressure fluid from the pump is directed above the diaphragm, applying force to close the valve.
    The valve closes slowly as fluid from the lower diaphragm chamber is gradually released to atmosphere through speed control ¡°C" and solenoid valve 2.
    When the valve closes fully, the limit switch ¡°E" shuts off the pump by electrical signal.

 

 

¢º Dimensions 

 

Globe Type

Angle Type

Valve Size (mm) 

50

80

100

150

200

250

300

 When Ordering,
      Please Specify

  1. Model No.
  2. Valve Size
  3. Pattern : Globe or Angle
  4. Working Pressure
  5. Screwed or Flanged
  6. Desired Materials
  7. Desired Options
  8. Solenoid Valve Specification

 A Screwed

238

318

-

-

-

-

-

 AA 10kgf/§²

238

305

381

508

645

756

864

 B

78

93

105

140

165

200

223

 Cmax

200