Specifications & Materials Descriptions & Typical Applications
Sequence of Operation Dimentions & Installation
|

|
¡Ü Provides quick check action
¡Ü Operates using pressure in the pipe
¡Ü Adjustable the speed of opening and closing separately
Booster Pump Control Valve is designed for installation on booster pump's discharge side to prevent starting and stopping pressure surges in the pipeline while the pump starts and stops.
If power failure occurs, the valve immediately closes preventing return flow, regardless of control mode.
|
* Korea Patent No. : 0479297
|
Specifications
|
Screwed
KSPT(BSP) - NPT Standard
|
Flanged
10kgf/§² - ANSI 150 Standard |
|
Globe
|
50A(2¢©) ¢¦80A(3¢©)
|
50A(2¢©) ¢¦300A(12¢©) |
|
Angle
|
50A(2¢©) ¢¦80A(3¢©)
|
50A(2¢©) ¢¦300A(12¢©) |
|
|
KS D 1513. Class 10
|
ANSI B 16.42 Class 150 |
|
Operating Pressure
|
0.05¢¦1.5 MPa(0.5~15kg f/§²)
|
7¢¦213 PSIG |
|
Media
|
Temperature : 0°C ~ 80°C Water, Oil (Order-Made)
|
|
Compartment
|
Material Options |
|
Body & Cover
|
Ductile Iron
|
SSC13 |
|
Diaphragm Washer & Disc
|
Cast Iron
|
SSC13 |
|
Cover Plug & Bearing
|
Brass
|
STS304 |
|
Shaft & Seat
|
STS304 |
|
Diaphragm
|
Nylon reinforced N.R
|
|
Disc Seal
|
N.R |
|
Note : · NSF/ANSI Standard 61 Epoxy Coating standard
· Nylon 11 Coating available (Rilsan Coating) : optional |
|
¢º Solenoid Control Valve Specifications
|
|
Voltage
|
24, 110, 220 AC 60Hz or 50Hz / 12, 24 DC |
|
Operating Pressure
|
1.5 MPa (213 PSIG) |
|
Coil Insulation
|
Coil Insulation Class B(Standard) H(Optional) |
|
Power Supply
|
AC 8 Watts / DC 12 Watts |

|
Item
|
Description |
|
1 |
BALEM 130 (Basic Valve) |
|
2 |
Strainer |
|
3
|
Cock Valve |
|
4
|
Suttle Valve |
|
5
|
3-Way Solenoid control Valve |
|
6
|
Flow Control Valve |
| 7
|
3-Way Solenoid control Valve |
| 8
|
Flow Control Valve |
|
9
|
Cock Valve |
|
10
|
Flow Clean Strainer |

Control Diagram
¡Ø Click E-catalog to Download. 
|
¡Ü Pump Off
With pump off, static line pressure is transmitted through strainer ¡°F"¡æshuttle Valve ¡°B"¡æsolenoid valve 1¡æspeed control ¡°D"¡æthe chamber above the diaphragm, thus holding the valve closed.
If power failure occurs, the valve closes immediately to prevent reverse flow, regardless of control mode.
|

|
|
¡Ü Starting Cycle
Starting switch closes, pump starts, solenoid control valve 1 energizes and shifts allowing fluid from upper diaphragm chamber to drain to atmosphere.
High pressure fluid from pump enters strainer "A"¡æshuttle valve ¡°B"¡æsolenoid valve 2¡æspeed control valve ¡°C"¡æHigh pressure fluid is transmitted to the lower diaphragm chamber and opens the valve slowly.
|

|
|
¡Ü Stopping Cycle
Starting switch opens, solenoid control 2 de-energizes and shifts, pump continues to run. High Pressure fluid from the pump is directed above the diaphragm, applying force to close the valve.
The valve closes slowly as fluid from the lower diaphragm chamber is gradually released to atmosphere through speed control ¡°C" and solenoid valve 2. When the valve closes fully, the limit switch ¡°E" shuts off the pump by electrical signal.
|

|

|

Globe Type
|

Angle Type
|
|
Valve Size (mm)
|
50
|
80
|
100
|
150
|
200
|
250
|
300
|
When Ordering, Please Specify
1. Model No. 2. Valve Size 3. Pattern : Globe or Angle 4. Working Pressure 5. Screwed or Flanged 6. Desired Materials 7. Desired Options 8. Solenoid Valve Specification
|
|
A Screwed
|
238
|
318
|
-
|
-
|
-
|
-
|
- |
|
AA 10kgf/§²
|
238
|
305
|
381
|
508
|
645
|
756
|
864 |
|
B
|
78
|
93
|
105
|
140
|
165
|
200
|
223 |
|
Cmax
|
200 | |